• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 90 Indulink CU/ XLPE/ WS/ PVC 5 kV 100% and 133%

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket:black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy

Tecnical Data


COPPER CONDUCTOR, 5 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
837501045 4 0.21 0.469 0.531 0.794 488 953 97 110 3
837501047 2 0.27 0.522 0.585 0.878 662 1229 130 145 3
837501048 1 0.30 0.554 0.617 0.909 815 1410 155 170 3
837501049 1/0 0.33 0.591 0.654 0.946 1032 1658 180 195 3
837501050 2/0 0.37 0.631 0.694 0.986 1291 1948 205 220 3
837501051 3/0 0.42 0.677 0.740 1.032 1630 2324 240 250 3
837501052 4/0 0.47 0.731 0.794 1.086 2066 2799 280 290

3 ½

837501053 250 0.52 0.774 0.837 1.130 2433 3199 315 320

3 ½

837501054 350 0.61 0.869 0.932 1.224 3390 4221 385 385

3 ½

837501057 500 0.73 0.991 1.054 1.447 4868 5962 475 470 4
837501060 750 0.90 1.156 1.219 1.612 7359 8561 600 585 5
837501062 1000 1.06 1.312 1.375 1.828 9752 11268 690 670 6

COPPER CONDUCTOR, 5 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
839201045 4 0.21 0.489 0.552 0.844 488 1027 97 110 3
839201047 2 0.27 0.543 0.606 0.898 662 1258 130 145 3
839201048 1 0.30 0.574 0.637 0.930 815 1439 155 170 3
839201049 1/0 0.33 0.612 0.675 0.967 1032 1688 180 195 3
839201050 2/0 0.37 0.651 0.714 1.006 1291 1980 205 220 3
839201051 3/0 0.42 0.698 0.761 1.053 1630 2356 240 250 3
839201052 4/0 0.47 0.752 0.815 1.107 2066 2834 280 290

3 ½

839201053 250 0.52 0.795 0.858 1.150 2433 3234 315 320

3 ½

839201054 350 0.61 0.889 0.952 1.244 3390 4260 385 385

4

839201057 500 0.73 1.011 1.074 1.467 4868 6007 475 470 4
839201060 750 0.90 1.177 1.240 1.693 7359 8802 600 585 5
839201062 1000 1.06 1.332 1.395 1.848 9752 11325 690 670 6