MV 90 Indulink CU/ XLPE/ WS/ PVC 35 kV 100%

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket:black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy

Data


COPPER CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
837901049 1/0 0.33 1.081 1.144 1.436 1032 2548 195 200 4
837901050 2/0 0.37 1.120 1.183 1.476 1291 2866 225 230 5
837901051 3/0 0.42 1.167 1.230 1.522 1630 3274 260 260 5
837901052 4/0 0.47 1.221 1.284 1.576 2066 3787 295 295 5
837901053 250 0.52 1.264 1.327 1.619 2433 4217 330 325 5
837901054 350 0.61 1.359 1.422 1.774 3390 5505 395 390 5
837901057 500 0.73 1.481 1.544 1.996 4868 7428 480 465

6

837901060 750 0.90 1.646 1.709 2.162 7359 10161 585 565

6

837901062 1000 1.06 1.802 1.865 2.317 9752 12788 675 640

7