MV 90 Indulink CU/ XLPE/ WS/ PVC 25 kV 100% and 133%

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket:black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy

Data


COPPER CONDUCTOR, 25 kV 100 % INSULATION LEVEL, 260 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
837801048 1 0.30 0.874 0.937 1.229 815 1935 170 175 3 ½
837801049 1/0 0.33 0.911 0.974 1.266 1032 2200 195 200 3 ½
837801050 2/0 0.37 0.950 1.013 1.306 1291 2509 225 230 4
837801051 3/0 0.42 0.997 1.060 1.352 1630 2905 260 260 4
837801052 4/0 0.47 1.051 1.114 1.406 2066 3405 295 295 4
837801053 250 0.52 1.094 1.157 1.449 2433 3825 330 325 5
837801054 350 0.61 1.189 1.252 1.544 3390 4891 395 390

5

837801057 500 0.73 1.311 1.374 1.826 4868 6939 480 465

5

837801060 750 0.90 1.476 1.539 1.992 7359 9632 585 565

6

837801062 1000 1.06 1.631 1.694 2.147 9752 12222 675 640 6

COPPER CONDUCTOR, 25 kV 133 % INSULATION LEVEL, 320 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
839501048 1 0.30 0.994 1.057 1.349 815 2171 170 175 4
839501049 1/0 0.33 1.031 1.094 1.387 1032 2442 195 200 4
839501050 2/0 0.37 1.071 1.134 1.426 1291 2757 225 230 4
839501051 3/0 0.42 1.117 1.180 1.472 1630 3162 260 260 5
839501052 4/0 0.47 1.171 1.234 1.526 2066 3672 295 295 5
839501053 250 0.52 1.215 1.278 1.570 2433 4098 330 325 5
839501054 350 0.61 1.309 1.372 1.724 3390 5374 395 390

5

839501057 500 0.73 1.431 1.494 1.947 4868 7281 480 465

6

839501060 750 0.90 1.596 1.659 2.112 7359 10002 585 565

6

839501062 1000 1.06 1.752 1.815 2.268 9752 12619 675 640 7