MV 90 Indulink CU/ XLPE/ CT/ LLDPE 8 kV 100% and 133% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black sunlight linear low density thermoplastic polyethylene (LLDPE).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable.

Data


COPPER CONDUCTOR, 8 kV 100 % INSULATION LEVEL, 115 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
82110104540.210.5180.5810.7273203521101153
82110104720.270.5720.6350.7814464541501553
82110104810.300.6040.6670.8425325391701753
8211010491/00.330.6410.7040.8806406241952003
8211010502/00.370.6800.7430.9197767302252303
8211010513/00.420.7270.7900.9669458602602603
8211010524/00.470.7810.8441.02011581023295300

3

8211010532500.520.8240.8871.06313441164330335

3

8211010543500.610.9190.9811.15718221522395415

3 ½

8211010575000.731.0411.1041.279255420624804654
8211010607500.901.2061.2691.445375029335855655
82110106210001.061.3611.4241.600494738036756405

COPPER CONDUCTOR, 8 kV 133 % INSULATION LEVEL, 140 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
82290104540.210.5690.6310.7773303811101153
82290104720.270.6220.6850.8614575021501553
82290104810.300.6540.7170.8935435721701753
8229010491/00.330.6910.7540.9306516591952003
8229010502/00.370.7310.7940.9707877662252303
8229010513/00.420.7770.8401.0169568972602603
8229010524/00.470.8310.8941.07011681062295300

3

8229010532500.520.8740.9371.11313551205330335

3 ½

8229010543500.610.9691.0321.20818331565395415

3 ½

8229010575000.731.0911.1541.330256521094804654
8229010607500.901.2561.3191.495376029865855655
82290106210001.061.4121.4751.711495839266756405