• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 90 Indulink CU/ XLPE/ CT/ PVC 5 kV 100% and 133% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable.

Data


COPPER CONDUCTOR, 5 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
837001045 4 0.21 0.469 0.531 0.677 309 759 97 110 3
837001047 2 0.27 0.522 0.585 0.731 436 986 130 145 3
837001048 1 0.30 0.554 0.617 0.763 522 1136 155 170 3
837001049 1/0 0.33 0.591 0.654 0.800 630 1325 180 195 195 3
837001050 2/0 0.37 0.631 0.694 0.870 765 1605 205 220 225 3
837001051 3/0 0.42 0.677 0.740 0.916 934 1895 240 250 260 3
837001052 4/0 0.47 0.731 0.794 0.970 1147 2256 280 290 300

3

837001053 250 0.52 0.774 0.837 1.013 1333 2569 315 320 335

3

837001054 350 0.61 0.869 0.932 1.108 1812 3362 385 385 415

3 ½

837001057 500 0.73 0.991 1.054 1.230 2543 4558 475 470 520 3 ½
837001060 750 0.90 1.156 1.219 1.395 3739 6489 600 585 675 4
837001062 1000 1.06 1.312 1.375 1.551 4937 8417 690 670 805 5

COPPER CONDUCTOR, 5 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
838801045 4 0.21 0.489 0.552 0.698 313 785 97 110 3
838801047 2 0.27 0.543 0.606 0.752 440 1013 130 145 3
838801048 1 0.30 0.574 0.637 0.783 526 1165 155 170 3
838801049 1/0 0.33 0.612 0.675 0.851 634 1403 180 195 195 3
838801050 2/0 0.37 0.651 0.714 0.890 770 1637 205 220 225 3
838801051 3/0 0.42 0.698 0.761 0.937 939 1928 240 250 260 3
838801052 4/0 0.47 0.752 0.815 0.990 1151 2290 280 290 300

3

838801053 250 0.52 0.795 0.858 1.034 1338 2605 315 320 335

3

838801054 350 0.61 0.889 0.952 1.128 1816 3401 385 385 415

3 ½

838801057 500 0.73 1.011 1.074 1.250 2548 4600 475 470 520 4
838801060 750 0.90 1.177 1.240 1.416 3743 6537 600 585 675 4
838801062 1000 1.06 1.332 1.395 1.571 4941 8469 690 670 805 5