Share:     

Download:

MV 90 Indulink CU/ XLPE/ CT/ PVC 35 kV 100% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable.

Data


COPPER CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)TRAY (3)
8374010491/00.331.0811.1441.32073522721952001954
8374010502/00.371.1201.1831.35987025332252302254
8374010513/00.421.1671.2301.4061.03928542602602604
8374010524/00.471.2211.2841.460125232532952953005
8374010532500.521.2641.3271.503143835973303253305
8374010543500.611.3591.4221.598191744563953904105
8374010575000.731.4811.5441.77926485938480465510

5

8374010607500.901.6461.7091.94538448004585565655

6

83740106210001.061.8021.8652.1005042100586756407806