• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 90 Indulink CU/ XLPE/ CT/ PVC 35 kV 100% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable.

Data


COPPER CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
837401049 1/0 0.33 1.081 1.144 1.320 735 2272 195 200 195 4
837401050 2/0 0.37 1.120 1.183 1.359 870 2533 225 230 225 4
837401051 3/0 0.42 1.167 1.230 1.406 1.039 2854 260 260 260 4
837401052 4/0 0.47 1.221 1.284 1.460 1252 3253 295 295 300 5
837401053 250 0.52 1.264 1.327 1.503 1438 3597 330 325 330 5
837401054 350 0.61 1.359 1.422 1.598 1917 4456 395 390 410 5
837401057 500 0.73 1.481 1.544 1.779 2648 5938 480 465 510

5

837401060 750 0.90 1.646 1.709 1.945 3844 8004 585 565 655

6

837401062 1000 1.06 1.802 1.865 2.100 5042 10058 675 640 780 6