MV 90 Indulink CU/ XLPE/ CT/ LLDPE 5 kV 100% and 133% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black sunlight linear low density thermoplastic polyethylene (LLDPE).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable.

Data


COPPER CONDUCTOR, 5 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
82100104540.210.4690.5310.677309324971103
82100104720.270.5220.5850.7314364251301453
82100104810.300.5540.6170.7635224921551703
8210010491/00.330.5910.6540.8006305761801953
8210010502/00.370.6310.6940.8707656962052203
8210010513/00.420.6770.7400.9169348252402503
8210010524/00.470.7310.7940.9701147986280300

3

8210010532500.520.7740.8371.01313331126315335

3

8210010543500.610.8690.9321.10818121481385415

3 ½

8210010575000.730.9911.0541.230254320164754703 ½
8210010607500.901.1561.2191.395373928836005854
82100106210001.061.3121.3751.551493737476906705

COPPER CONDUCTOR, 5 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
82280104540.210.4890.5520.698313335971103
82280104720.270.5430.6060.7524404371301453
82280104810.300.5740.6370.7835265051551703
8228010491/00.330.6120.6750.8516346051801953
8228010502/00.370.6510.7140.8907707102052203
8228010513/00.420.6980.7610.9379398392402503
8228010524/00.470.7520.8150.99011511001280300

3

8228010532500.520.7950.8581.03413381142315335

3

8228010543500.610.8890.9521.12818161497385415

3 ½

8228010575000.731.0111.0741.250254820354754704
8228010607500.901.1771.2401.416374329036005854
82280106210001.061.3321.3951.571494137706906705