MV 90 Indulink CU/ XLPE / WS/ LLDPE 25 kV 100% and 133%

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket:black sunlight linear low density thermoplastic polyethylene (LLDPE).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy

Data


COPPER CONDUCTOR, 25 kV 100 % INSULATION LEVEL, 260 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
82180104810.300.8740.9371.2298158151701753 ½
8218010491/00.330.9110.9741.26610329331952003 ½
8218010502/00.370.9501.0131.306129110712252304
8218010513/00.420.9971.0601.352163012492602604
8218010524/00.471.0511.1141.406206614742952954
8218010532500.521.0941.1571.449243316623303255
8218010543500.611.1891.2521.54433902141395390

5

8218010575000.731.3111.3741.82648683014480465

5

8218010607500.901.4761.5391.99273594225585565

6

82180106210001.061.6311.6942.147975253906756406

COPPER CONDUCTOR, 25 kV 133 % INSULATION LEVEL, 320 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
82350104810.300.9941.0571.3498159151701754
8235010491/00.331.0311.0941.387103210361952004
8235010502/00.371.0711.1341.426129111772252304
8235010513/00.421.1171.1801.472163013582602605
8235010524/00.471.1711.2341.526206615872952955
8235010532500.521.2151.2781.570243317783303255
8235010543500.611.3091.3721.72433902330395390

5

8235010575000.731.4311.4941.94748683158480465

6

8235010607500.901.5961.6592.11273594382585565

6

82350106210001.061.7521.8152.268975255596756407