• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 90 Indulink AL/ XLPE/ WS/ PVC 35 kV 100%

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: one-third neutral concentric round annealed bare copper wires elically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energyc

Data


ALUMINUM CONDUCTOR. 35 kV 100 % INSULATION LEVEL. 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
841501049 1/0 0.33 1.081 1.144 1.436 223 196 1946 150 155 4
841501050 2/0 0.37 1.120 1.183 1.476 279 229 2099 175 175 5
841501051 3/0 0.42 1.167 1.230 1.522 354 295 2311 200 200 5
841501052 4/0 0.47 1.221 1.284 1.576 445 360 2552 230 230

5

841501053 250 0.52 1.264 1.327 1.619 527 426 2766 255 250

5

841501054 350 0.61 1.359 1.422 1.774 736 589 3482 310 305

5

841501057 500 0.73 1.481 1.544 1.896 1061 819 4233 385 370 6
841501060 750 0.90 1.646 1.709 2.162 1592 1252 5743 485 455 6
841501062 1000 1.06 1.802 1.865 2.317 2133 1670 6959 565 525 7