MV 90 Indulink AL/ XLPE/ WS/ PVC 25 kV 100% and 133%

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: one-third neutral concentric round annealed bare copper wires elically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energyc

Data


ALUMINUM CONDUCTOR, 25 kV 100 % INSULATION LEVEL. 260 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
841401048 1 0.30 0.874 0.937 1.229 176 196 1497 130 135 3 ½
841401049 1/0 0.33 0.911 0.974 1.266 223 196 1599 150 155 3 ½
841401050 2/0 0.37 0.950 1.013 1.306 279 229 1742 175 175 4
841401051 3/0 0.42 0.997 1.060 1.352 354 295 1942 200 200 4
841401052 4/0 0.47 1.051 1.114 1.406 445 360 2171 230 230

4

841401053 250 0.52 1.094 1.157 1.449 527 426 2374 255 250

5

841401054 350 0.61 1.189 1.252 1.544 736 589 2867 310 305

5

841401057 500 0.73 1.311 1.374 1.726 1061 819 3769 385 370 5
841401060 750 0.90 1.476 1.539 1.992 1592 1252 5214 485 455 5
841401062 1000 1.06 1.631 1.694 2.147 2133 1670 6393 565 525 6

ALUMINUM CONDUCTOR, 25 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
842301048 1 0.30 0.994 1.057 1.349 176 196 1732 130 135 3 ½
842301049 1/0 0.33 1.031 1.094 1.387 223 196 1841 150 155 4
842301050 2/0 0.37 1.071 1.134 1.426 279 229 1990 175 175 4
842301051 3/0 0.42 1.117 1.180 1.472 354 295 2199 200 200 4
842301052 4/0 0.47 1.171 1.234 1.526 445 360 2437 230 230

5

842301053 250 0.52 1.215 1.278 1.570 527 426 2648 255 250

5

842301054 350 0.61 1.309 1.372 1.724 736 589 3351 310 305

5

842301057 500 0.73 1.431 1.494 1.846 1061 819 4093 385 370 6
842301060 750 0.90 1.596 1.659 2.112 1592 1252 5585 485 455 6
842301062 1000 1.06 1.752 1.815 2.268 2133 1670 6790 565 525 7