Share:     

Download:

MV 90 Indulink AL/ XLPE/ WS/ PVC 25 kV 100% and 133%

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: one-third neutral concentric round annealed bare copper wires elically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energyc

Data


ALUMINUM CONDUCTOR, 25 kV 100 % INSULATION LEVEL. 260 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
84140104810.300.8740.9371.22917619614971301353 ½
8414010491/00.330.9110.9741.26622319615991501553 ½
8414010502/00.370.9501.0131.30627922917421751754
8414010513/00.420.9971.0601.35235429519422002004
8414010524/00.471.0511.1141.4064453602171230230

4

8414010532500.521.0941.1571.4495274262374255250

5

8414010543500.611.1891.2521.5447365892867310305

5

8414010575000.731.3111.3741.726106181937693853705
8414010607500.901.4761.5391.9921592125252144854555
84140106210001.061.6311.6942.1472133167063935655256

ALUMINUM CONDUCTOR, 25 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
84230104810.300.9941.0571.34917619617321301353 ½
8423010491/00.331.0311.0941.38722319618411501554
8423010502/00.371.0711.1341.42627922919901751754
8423010513/00.421.1171.1801.47235429521992002004
8423010524/00.471.1711.2341.5264453602437230230

5

8423010532500.521.2151.2781.5705274262648255250

5

8423010543500.611.3091.3721.7247365893351310305

5

8423010575000.731.4311.4941.846106181940933853706
8423010607500.901.5961.6592.1121592125255854854556
84230106210001.061.7521.8152.2682133167067905655257