Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: one-third neutral concentric round annealed bare copper wires elically applied over the insulation shield.
6- Jacket: black sunlight linear low density thermoplastic polyethylene (LLDPE).

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energyc

Data


ALUMINUM CONDUCTOR. 35 kV 100 % INSULATION LEVEL. 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
829101049 1/0 0.33 1.081 1.144 1.436 223 196 808 150 155 4
829101050 2/0 0.37 1.120 1.183 1.476 279 229 875 175 175 5
829101051 3/0 0.42 1.167 1.230 1.522 354 295 969 200 200 5
829101052 4/0 0.47 1.221 1.284 1.576 445 360 1076 230 230

5

829101053 250 0.52 1.264 1.327 1.619 527 426 1234 255 250

5

829101054 350 0.61 1.359 1.422 1.774 736 589 1468 310 305

5

829101057 500 0.73 1.481 1.544 1.896 1061 819 1801 385 370 6
829101060 750 0.90 1.646 1.709 2.162 1592 1252 2443 485 455 6
829101062 1000 1.06 1.802 1.865 2.317 2133 1670 2985 565 525 7