MV 90 Indulink AL / XLPE / CT / LLDPE 5 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black sunlight linear low density thermoplastic polyethylene (LLDPE).

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric EnergyUL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables
IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 5 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
828201045 4 0.21 0.469 0.531 0.677 88 117 232 76 86 3
828201047 2 0.27 0.522 0.585 0.731 140 129 278 100 115 3
828201048 1 0.30 0.554 0.617 0.763 176 136 307 120 130 3
828201049 1/0 0.33 0.591 0.654 0.800 223 144 344 140 150 3
828201050 2/0 0.37 0.631 0.694 0.870 279 152 402 160 170 3
828201051 3/0 0.42 0.677 0.740 0.916 354 162 456 190 195 3
828201052 4/0 0.47 0.731 0.794 0.970 445 174 520 215 230

3

828201053 250 0.52 0.774 0.837 1.013 527 183 576 250 260

3

828201054 350 0.61 0.869 0.932 1.108 736 204 711 305 320

3 ½

828201057 500 0.73 0.991 1.054 1.230 1061 230 910 380 370 3 ½
828201060 750 0.90 1.156 1.219 1.395 1592 266 1221 490 470 4
828201062 1000 1.06 1.312 1.375 1.551 2133 300 1532 580 545 5

ALUMINUM CONDUCTOR, 5 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
830001045 4 0.21 0.489 0.552 0.698 88 121 243 76 86 3
830001047 2 0.27 0.543 0.606 0.752 140 133 290 100 115 3
830001048 1 0.30 0.574 0.637 0.783 176 140 319 120 130 3
830001049 1/0 0.33 0.612 0.675 0.851 223 148 373 140 150 3
830001050 2/0 0.37 0.651 0.714 0.890 279 157 416 160 170 3
830001051 3/0 0.42 0.698 0.761 0.937 354 167 470 190 195 3
830001052 4/0 0.47 0.752 0.815 0.990 445 178 535 215 230

3

830001053 250 0.52 0.795 0.858 1.034 527 188 591 250 260

3

830001054 350 0.61 0.889 0.952 1.128 736 208 728 305 305

3 ½

830001057 500 0.73 1.011 1.074 1.250 1061 235 928 380 370 3 ½
830001060 750 0.90 1.177 1.240 1.416 1592 270 1242 490 470 4
830001062 1000 1.06 1.332 1.395 1.571 2133 304 1555 580 545 5