MV 90 Indulink AL / XLPE / CT / LLDPE 35 kV 100% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black sunlight linear low density thermoplastic polyethylene (LLDPE).

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric EnergyUL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables
IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
828601049 1/0 0.33 1.081 1.144 1.320 223 249 748 150 150 4
828601050 2/0 0.37 1.120 1.183 1.359 279 257 803 175 170 4
828601051 3/0 0.42 1.167 1.230 1.406 354 267 871 200 200 4
828601052 4/0 0.47 1.221 1.284 1.460 445 279 953 230 230 5
828601053 250 0.52 1.264 1.327 1.503 527 288 1022 255 260 5
828601054 350 0.61 1.359 1.422 1.598 736 309 1187 310 320 5
828601057 500 0.73 1.481 1.544 1.779 1061 335 1492 385 395

5

828601060 750 0.90 1.646 1.709 1.945 1592 371 1862 485 455

6

828601062 1000 1.06 1.802 1.865 2.100 2133 405 2228 565 525 6