• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 90 Indulink AL / XLPE / CT / LLDPE 8 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black sunlight linear low density thermoplastic polyethylene (LLDPE).

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric EnergyUL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables
IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 8 kV 100 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
828301045 4 0.21 0.518 0.581 0.727 88 128 260 84 91 3
828301047 2 0.27 0.572 0.635 0.781 140 139 307 115 120 3
828301048 1 0.30 0.604 0.667 0.842 176 146 353 130 135 3
828301049 1/0 0.33 0.641 0.704 0.880 223 154 392 150 155 3
828301050 2/0 0.37 0.680 0.743 0.919 279 163 436 175 175 3
828301051 3/0 0.42 0.727 0.790 0.966 354 173 491 200 200 3
828301052 4/0 0.47 0.781 0.844 1.020 445 185 557 230 230

3

828301053 250 0.52 0.824 0.887 1.063 527 194 614 255 250

3

828301054 350 0.61 0.919 0.981 1.157 736 214 752 310 305

3 ½

828301057 500 0.73 1.041 1.104 1.279 1061 241 955 385 370 4
828301060 750 0.90 1.206 1.269 1.445 1592 277 1272 485 455 5
828301062 1000 1.06 1.361 1.424 1.600 2133 310 1588 565 525 5

ALUMINUM CONDUCTOR, 8 kV 133 % INSULATION LEVEL, 140 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
830101045 4 0.21 0.569 0.631 0.777 88 138 289 84 91 3
830101047 2 0.27 0.622 0.685 0.861 140 150 355 115 120 3
830101048 1 0.30 0.654 0.717 0.893 176 157 387 130 135 3
830101049 1/0 0.33 0.691 0.754 0.930 223 165 427 150 155 3
830101050 2/0 0.37 0.731 0.794 0.970 279 174 471 175 175 3
830101051 3/0 0.42 0.777 0.840 1.016 354 184 528 200 200 3
830101052 4/0 0.47 0.831 0.894 1.070 445 195 596 230 230

3

830101053 250 0.52 0.874 0.937 1.113 527 205 654 255 250

3 ½

830101054 350 0.61 0.969 1.032 1.208 736 225 796 310 320

3 ½

830101057 500 0.73 1.091 1.154 1.330 1061 252 1003 385 370 4
830101060 750 0.90 1.256 1.319 1.495 1592 287 1324 485 455 5
830101062 1000 1.06 1.412 1.395 1.711 2133 321 1710 565 525 5