• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 90 EPRONAX CU/ EPR/ WS/ LLDPE 35 kV 100%

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper tape shield: one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket: black sunlight linear low density thermoplastic polyethylene (LLDPE).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy

Tecnical Data


COPPER CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
820901049 1/0 0.33 1.081 1.144 1.436 1032 1164 195 200 4
820901050 2/0 0.37 1.120 1.183 1.476 1291 1311 225 230 5
820901051 3/0 0.42 1.167 1.230 1.522 1630 1499 260 260 5
820901052 4/0 0.47 1.221 1.284 1.576 2066 1735 295 295 5
820901053 250 0.52 1.264 1.327 1.619 2433 1933 330 325

5

820901054 350 0.61 1.359 1.422 1.774 3390 2501 395 390

5

820901057 500 0.73 1.481 1.544 1.996 4868 3348 480 465

6

820901060 750 0.90 1.646 1.709 2.162 7359 4597 585 565 6
820901062 1000 1.06 1.802 1.865 2.317 9752 5796 675 640 7