MV 90 EPRONAX CU/ EPR/ CT/ PVC 35 kV 100% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper tape shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy. UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


COPPER CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
836401049 1/0 0.33 1.081 1.144 1.320 986 2456 195 200 195 4
836401050 2/0 0.37 1.120 1.183 1.359 1188 2727 225 230 225 4
836401051 3/0 0.42 1.167 1.230 1.406 1439 3060 260 260 260 4
836401052 4/0 0.47 1.221 1.284 1.460 1756 3472 295 295 300 5
836401053 250 0.52 1.264 1.327 1.503 2034 3827 330 325 330 5
836401054 350 0.61 1.359 1.422 1.598 2750 4710 395 390 410 5
836401057 500 0.73 1.481 1.544 1.779 3846 6222 480 465 510

5

836401060 750 0.90 1.646 1.709 1.945 5643 8330 585 565 655

6

836401062 1000 1.06 1.802 1.865 2.100 7443 10423 675 640 780 6