MV 90 EPRONAX CU/ EPR/ CT/ PVC 15 kV 100% and 133% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper tape shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy. UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


COPPER CONDUCTOR, 15 kV 100 % INSULATION LEVEL, 175 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)TRAY (3)
83620104720.270.6820.7450.92162913371501553
83620104810.300.7140.7770.95375615001701753
8362010491/00.330.7510.8140.99091617041952001953
8362010502/00.370.7910.8541.029111719522252302253
8362010513/00.420.8370.9001.076136822582602602603
8362010524/00.470.8910.9541.130168526382952953003 ½
8362010532500.520.9340.9971.17319632967330325335

3 ½

8362010543500.611.0291.0921.26826793794395390415

4

8362010575000.731.1511.2141.39037755035480465515

4

8362010607500.901.3161.3791.555557270265855656655
83620106210001.061.4721.5351.770737292106756407955

COPPER CONDUCTOR, 15 kV 133 % INSULATION LEVEL, 220 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)TRAY (3)
83820104720.270.7720.8351.01164815111501553
83820104810.300.8040.8671.04277516801701753
8382010491/00.330.8410.9041.08093518901952001953
8382010502/00.370.8800.9431.119113621442252302253
8382010513/00.420.9270.9901.166138824572602602603 ½
8382010524/00.470.9811.0441.220170428462952953003 ½
8382010532500.521.0241.0871.26319823182330325335

4

8382010543500.611.1191.1811.35726984024395390415

4

8382010575000.731.2411.3041.47937955284480465515

5

8382010607500.901.4061.4691.705559174945855656655
83820106210001.061.5611.6241.860739295216756407956