MV 90 EPRONAX CU/ EPR/ CT/ LLDPE 5 kV 100% and 133% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper tape shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black sunlight linear low density thermoplastic polyethylene (LLDPE).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy. UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


COPPER CONDUCTOR, 5 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
820001045 4 0.21 0.469 0.531 0.677 408 337 97 110 3
820001047 2 0.27 0.522 0.585 0.761 595 440 130 145 3
820001048 1 0.30 0.554 0.617 0.793 721 508 155 170 3
820001049 1/0 0.33 0.591 0.654 0.830 881 593 180 195 3
820001050 2/0 0.37 0.631 0.694 0.870 1083 714 205 220 3
820001051 3/0 0.42 0.677 0.740 0.916 1334 845 240 250 3
820001052 4/0 0.47 0.731 0.794 0.970 1651 1008 280 290

3

820001053 250 0.52 0.774 0.837 1.013 1929 1149 315 320

3

820001054 350 0.61 0.869 0.932 1.108 2644 1507 385 385

3 ½

820001057 500 0.73 0.991 1.054 1.230 3741 2047 475 470 3 ½
820001060 750 0.90 1.156 1.219 1.395 5538 2919 600 585 4
820001062 1000 1.06 1.312 1.375 1.551 7338 3789 690 670 5

COPPER CONDUCTOR, 5 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
822001045 4 0.21 0.489 0.552 0.698 413 350 97 110 3
822001047 2 0.27 0.543 0.606 0.752 599 453 130 145 3
822001048 1 0.30 0.574 0.637 0.783 726 522 155 170 3
822001049 1/0 0.33 0.612 0.675 0.851 886 624 180 195 3
822001050 2/0 0.37 0.651 0.714 0.890 1087 730 205 220 3
822001051 3/0 0.42 0.698 0.761 0.937 1338 861 240 250 3
822001052 4/0 0.47 0.752 0.815 0.990 1655 1025 280 290

3

822001053 250 0.52 0.795 0.858 1.034 1933 1167 315 320

3

822001054 350 0.61 0.889 0.952 1.128 2649 1527 385 385

3 ½

822001057 500 0.73 1.011 1.074 1.250 3745 2069 475 470 4
822001060 750 0.90 1.177 1.240 1.416 5542 2943 600 585 4
822001062 1000 1.06 1.332 1.395 1.571 7342 3816 690 670 5