• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 90 EPRONAX CU/ EPR/ CT/ LLDPE 35 kV 100% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper tape shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black sunlight linear low density thermoplastic polyethylene (LLDPE).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy. UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


COPPER CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
820401049 1/0 0.33 1.081 1.144 1.320 986 1064 195 200 4
820401050 2/0 0.37 1.120 1.183 1.359 1188 1185 225 230 4
820401051 3/0 0.42 1.167 1.230 1.406 1439 1334 260 260 4
820401052 4/0 0.47 1.221 1.284 1.460 1756 1518 295 295 5
820401053 250 0.52 1.264 1.327 1.503 2034 1677 330 325 5
820401054 350 0.61 1.359 1.422 1.598 2750 2072 395 390 5
820401057 500 0.73 1.481 1.544 1.779 3846 2727 480 465

5

820401060 750 0.90 1.646 1.709 1.945 5643 3671 585 565

6

820401062 1000 1.06 1.802 1.865 2.100 7443 4608 675 640 6