MV 90 EPRONAX AL/ EPR/ WS/ PVC 8 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

STM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy

Data


ALUMINUM CONDUCTOR, 8 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
840201045 4 0.21 0.518 0.581 0.873 88 196 899 84 91 3
840201047 2 0.27 0.572 0.635 0.927 140 196 1015 115 120 3
840201048 1 0.30 0.604 0.667 0.959 176 196 1088 130 135 3
840201049 1/0 0.33 0.641 0.704 0.996 223 196 1179 150 155 150 3
840201050 2/0 0.37 0.680 0.743 1.035 279 229 1311 175 175 170 3
840201051 3/0 0.42 0.727 0.790 1.082 354 295 1498 200 200 200 3
840201052 4/0 0.47 0.781 0.844 1.136 445 360 1710 230 230 230

3

840201053 250 0.52 0.824 0.887 1.179 527 426 1901 255 250 260

3

840201054 350 0.61 0.919 0.981 1.274 736 589 2367 310 305 320

3 ½

840201057 500 0.73 1.041 1.104 1.396 1061 819 3038 385 370 400 4
840201060 750 0.90 1.206 1.269 1.722 1592 1252 4561 485 455 525 5
840201062 1000 1.06 1.361 1.424 1.877 2133 1670 5694 565 525 630 5

ALUMINUM CONDUCTOR, 8 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
842101045 4 0.21 0.569 0.631 0.924 88 196 980 84 91 3
842101047 2 0.27 0.622 0.685 0.978 140 196 1100 115 120 3
842101048 1 0.30 0.654 0.717 1.009 176 196 1176 130 135 3
842101049 1/0 0.33 0.691 0.754 1.046 223 196 1271 150 155 150 3
842101050 2/0 0.37 0.731 0.794 1.086 279 229 1406 175 175 175 3
842101051 3/0 0.42 0.777 0.840 1.132 354 295 1597 200 200 200 3
842101052 4/0 0.47 0.831 0.894 1.186 445 360 1815 230 230 230

3

842101053 250 0.52 0.874 0.937 1.230 527 426 2009 255 250 260

3 ½

842101054 350 0.61 0.969 1.032 1.324 736 589 2483 310 305 320

3 ½

842101057 500 0.73 1.091 1.154 1.446 1061 819 3166 385 370 400 4
842101060 750 0.90 1.256 1.319 1.772 1592 1252 4716 485 455 525 5
842101062 1000 1.06 1.412 1.475 1.928 2133 1670 5863 565 525 630 5