MV 90 EPRONAX AL/ EPR/ WS/ LLDPE 25 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

STM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy

Data


ALUMINUM CONDUCTOR, 25 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
82800104810.300.8740.9371.2291761966691301353 ½
8280010491/00.330.9110.9741.2662231967161501553 ½
8280010502/00.370.9501.0131.3062792297821751753 ½
8280010513/00.420.9971.0601.3523542958752002003 ½
8280010524/00.471.0511.1141.406445360981230230

4

8280010532500.521.0941.1571.4495274261075255250

4

8280010543500.611.1891.2521.5447365891302310305

4

8280010575000.731.3111.3741.726106181916943853705
8280010607500.901.4761.5391.9921592125223244854555
82800106210001.061.6311.6942.1472133167028615655256

ALUMINUM CONDUCTOR, 25 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
82990104810.300.9941.0571.3491761967871301353 ½
8299010491/00.331.0311.0941.3872231968381501554
8299010502/00.371.0711.1341.4262792299081751754
8299010513/00.421.1171.1801.47235429510052002004
8299010524/00.471.1711.2341.5264453601116230230

4

8299010532500.521.2151.2781.5705274261214255250

5

8299010543500.611.3091.3721.7247365891516310305

5

8299010575000.731.4311.4941.846106181918583853705
8299010607500.901.5961.6592.1121592125225104854556
82990106210001.061.7521.8152.2682133167030635655256