MV 90 EPRONAX AL/ EPR/ CT/ PVC 35 kV 100% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - StandaASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


 ALUMINUM CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
840001049 1/0 0.33 1.081 1.144 1.320 223 249 1941 150 155 150 4
840001050 2/0 0.37 1.120 1.183 1.359 279 257 2076 175 175 170 4
840001051 3/0 0.42 1.167 1.230 1.406 354 267 2242 200 200 200 4
840001052 4/0 0.47 1.221 1.284 1.460 445 279 2440 230 230 230 5
840001053 250 0.52 1.264 1.327 1.460 527 288 2608 255 250 260 5
840001054 350 0.61 1.359 1.422 1.598 736 309 3005 310 305 320 5
840001057 500 0.73 1.481 1.544 1.779 1061 335 3772 385 370 395

5

840001060 750 0.90 1.646 1.709 1.945 1592 371 4651 485 455 515

6

840001062 1000 1.06 1.802 1.865 2.100 2133 405 5517 565 525 620 6