• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 90 EPRONAX AL/ EPR/ CT/ LLDPE 5 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (LLDPE).

Standards

ASTM B-400 - StandaASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 5 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
827201045 4 0.21 0.469 0.531 0.677 88 117 245 76 86
827201047 2 0.27 0.522 0.585 0.731 100 129 292 245 115
827201048 1 0.30 0.554 0.617 0.763 176 136 323 120 130
827201049 1/0 0.33 0.591 0.654 0.800 223 144 361 140 150 150
827201050 2/0 0.37 0.631 0.694 0.870 279 152 420 160 170 170
827201051 3/0 0.42 0.677 0.740 0.916 354 162 475 190 195 200
827201052 4/0 0.47 0.731 0.794 0.970 445 174 542 215 225 230
827201053 250 0.52 0.774 0.837 1.013 527 183 599 250 250 260
827201054 350 0.61 0.869 0.932 1.108 736 204 737 305 305 320
827201057 500 0.73 0.991 1.054 1.230 1061 230 941 380 370 410
827201060 750 0.90 1.156 1.219 1.395 1592 266 1257 490 470 530
827201062 1000 1.06 1.312 1.375 1.551 2133 300 1574 580 545 640

ALUMINUM CONDUCTOR, 5 kV 133 % INSULATION LEVEL, 115 MILS

 

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
829201045 4 0.21 0.489 0.552 0.698 88 121 258 76 86 3
829201047 2 0.27 0.543 0.606 0.752 140 133 306 100 115 3
829201048 1 0.30 0.574 0.637 0.783 176 140 337 120 130 3
829201049 1/0 0.33 0.612 0.675 0.851 223 148 392 140 150 3
829201050 2/0 0.37 0.651 0.714 0.890 279 157 436 160 170 3
829201051 3/0 0.42 0.698 0.761 0.937 354 167 492 190 195 3
829201052 4/0 0.47 0.752 0.815 0.990 445 178 559 215 225

3

829201053 250 0.52 0.795 0.858 1.034 527 188 617 250 250

3

829201054 350 0.61 0.889 0.952 1.128 736 208 757 320 305 3 ½
829201057 500 0.73 1.011 1.074 1.250 1061 235 962 380 370 3 ½
829201060 750 0.90 1.177 1.240 1.416 1592 270 1282 490 470 4
829201062 1000 1.06 1.332 1.395 1.571 2133 304 1601 580 545 5