Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket:black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy

Data


COPPER CONDUCTOR, 8 kV 100 % INSULATION LEVEL, 115 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
82520104540.210.5180.5810.87348810661201253
82520104720.270.5720.6350.92766212991651653
82520104810.300.6040.6670.95981514821901853
8252010491/00.330.6410.7040.996103217322152153
8252010502/00.370.6800.7431.035129120262552453
8252010513/00.420.7270.7901.082163024042902753
8252010524/00.470.7810.8441.136206628843303153 ½
8252010532500.520.8240.8871.179243332863653453 ½
8252010543500.610.9190.9811.274339043164404154
8252010575000.731.0411.1041.496486860725355005
8252010607500,901.2061.2691.722735988776556105
82520106210001.061.3611.4241.8779752114077556906

COPPER CONDUCTOR, 8 kV 133 % INSULATION LEVEL, 140 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
COPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
82690104540.210.5690.6310.92448811371201253
82690104720.270.6220.6850.97866213741651653
82690104810.300.6540.7171.00981515591901853
8269010491/00.330.6910.7541.046103218122152153
8269010502/00.370.7310.7941.086129121082552453
8269010513/00.420.7770.8401.132163024902902753 ½
8269010524/00.470.8310.8941.186206629733303153 ½
8269010532500.520.8740.9371.230243333793653453 ½
8269010543500.610.9691.0321.324339044154404154
8269010575000.731.0911.1541.547486861885355005
8269010607500,901.2561.3191.772735990106556105
82690106210001.061.4121.4751.9289752115517556906