MV 105 Indulink CU/ XLPE/ WS/ PVC 15 kV 100% and 133% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket:black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy

Data


COPPER CONDUCTOR, 15 kV 100 % INSULATION LEVEL, 175 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
825301047 2 0.27 0.682 0.745 1.069 662 1467 165 165 3
825301048 1 0.30 0.714 0.777 1.106 815 1655 190 185 3
825301049 1/0 0.33 0.751 0.814 1.146 1032 1911 215 215 3
825301050 2/0 0.37 0.791 0.854 1.192 1291 2210 255 245 3 ½
825301051 3/0 0.42 0.837 0.900 1.246 1630 2596 290 275 3 ½
825301052 4/0 0.47 0.891 0.954 1.289 2066 3084 330 315 3 ½
825301053 250 0.52 0.934 0.997 1.384 2433 3494 365 345

4

825301054 350 0.61 1.029 1.092 1.607 3390 4538 440 415

4

825301057 500 0.73 1.151 1.214 1.832 4868 6330 535 500

5

825301060 750 0.90 1.316 1.379 1.987 7359 9173 655 610 6
825301062 1000 1.06 1.472 1.535 1.069 9752 11727 755 690 6

COPPER CONDUCTOR, 15 kV 133 % INSULATION LEVEL, 220 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
827001047 2 0.27 0.772 0.835 1.127 662 1616 165 165 3 ½
827001048 1 0.30 0.804 0.867 1.159 815 1808 190 185 3 ½
827001049 1/0 0.33 0.841 0.904 1.196 1032 2069 215 215 3 ½
827001050 2/0 0.37 0.880 0.943 1.235 1291 2373 255 245 3 ½
827001051 3/0 0.42 0.927 0.990 1.282 1630 2765 290 275 3 ½
827001052 4/0 0.47 0.981 1.044 1.336 2066 3260 330 315 4
827001053 250 0.52 1.024 1.087 1.379 2433 3675 365 345

4

827001054 350 0.61 1.119 1.181 1.474 3390 4731 440 415

5

827001057 500 0.73 1.241 1.304 1.756 4868 6750 535 500

5

827001060 750 0.90 1.406 1.469 1.922 7359 9426 655 610 6
827001062 1000 1.06 1.561 1.624 2.077 9752 12000 755 690 6