MV 105 Indulink CU/ XLPE/ CT/ PVC 8 kV 100% and 133% I.L.
Construction
1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).
Standards
ASTM B-3 - Standard Speciï¬cation for Soft or Annealed Copper Wire
ASTM B-496 - Standard Speciï¬cation for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable.
Data
COPPER CONDUCTOR, 8 kV 100 % INSULATION LEVEL, 115 MILS
PRODUCT CODE | COND. SIZE (AWG or kcmil) | NOMINAL CONDUCTOR DIAMETER (inches) | NOMINAL INSULATION DIAM.(inches) | NOMINAL INSULATION SHIELD DIAM. (inches) | NOMINAL DIAMETER OVER JACKET (inches) | APPROX. WEIGHT (lb/kft) | AMPACITY (A) | CONDUIT SIZE (inches) | |||
---|---|---|---|---|---|---|---|---|---|---|---|
COPPER | TOTAL | CONDUIT IN AIR (1) | UNDERGROUND DUCT (2) | TRAY (3) | |||||||
824701045 | 4 | 0.21 | 0.518 | 0.581 | 0.727 | 320 | 823 | 120 | 125 | — | 3 |
824701047 | 2 | 0.27 | 0.572 | 0.635 | 0.781 | 436 | 1054 | 165 | 165 | — | 3 |
824701048 | 1 | 0.30 | 0.604 | 0.667 | 0.842 | 532 | 1255 | 190 | 185 | — | 3 |
824701049 | 1/0 | 0.33 | 0.641 | 0.704 | 0.880 | 640 | 1448 | 215 | 215 | 220 | 3 |
824701050 | 2/0 | 0.37 | 0.680 | 0.743 | 0.919 | 776 | 1684 | 255 | 245 | 250 | 3 |
824701051 | 3/0 | 0.42 | 0.727 | 0.790 | 0.966 | 945 | 1977 | 290 | 275 | 290 | 3 |
824701052 | 4/0 | 0.47 | 0.781 | 0.844 | 1.020 | 1158 | 2341 | 330 | 315 | 335 |
3 |
824701053 | 250 | 0.52 | 0.824 | 0.887 | 1.063 | 1344 | 2658 | 365 | 345 | 370 |
3 |
824701054 | 350 | 0.61 | 0.919 | 0.981 | 1.157 | 1822 | 3457 | 440 | 415 | 460 |
3 ½ |
824701057 | 500 | 0.73 | 1.041 | 1.104 | 1.279 | 2554 | 4662 | 535 | 500 | 575 | 4 |
824701060 | 750 | 0,90 | 1.206 | 1.269 | 1.445 | 3750 | 6605 | 655 | 610 | 745 | 5 |
824701062 | 1000 | 1.06 | 1.361 | 1.424 | 1.600 | 4947 | 8544 | 755 | 690 | 890 | 5 |
COPPER CONDUCTOR, 8 kV 133 % INSULATION LEVEL, 140 MILS
PRODUCT CODE | COND. SIZE (AWG or kcmil) | NOMINAL CONDUCTOR DIAMETER (inches) | NOMINAL INSULATION DIAM.(inches) | NOMINAL INSULATION SHIELD DIAM. (inches) | NOMINAL DIAMETER OVER JACKET (inches) | APPROX. WEIGHT (lb/kft) | AMPACITY (A) | CONDUIT SIZE (inches) | |||
---|---|---|---|---|---|---|---|---|---|---|---|
COPPER | TOTAL | CONDUIT IN AIR (1) | UNDERGROUND DUCT (2) | TRAY (3) | |||||||
826501045 | 4 | 0.21 | 0.569 | 0.631 | 0.777 | 330 | 892 | 120 | 125 | — | 3 |
826501047 | 2 | 0.27 | 0.622 | 0.685 | 0.861 | 457 | 1175 | 165 | 165 | — | 3 |
826501048 | 1 | 0.30 | 0.654 | 0.717 | 0.893 | 543 | 1332 | 190 | 185 | — | 3 |
826501049 | 1/0 | 0.33 | 0.691 | 0.754 | 0.930 | 651 | 1528 | 215 | 215 | 220 | 3 |
826501050 | 2/0 | 0.37 | 0.731 | 0.794 | 0.970 | 787 | 1767 | 255 | 245 | 250 | 3 |
826501051 | 3/0 | 0.42 | 0.777 | 0.840 | 1.016 | 956 | 2063 | 290 | 275 | 290 | 3 |
826501052 | 4/0 | 0.47 | 0.831 | 0.894 | 1.070 | 1168 | 2432 | 330 | 315 | 335 |
3 |
826501053 | 250 | 0.52 | 0.874 | 0.937 | 1.113 | 1355 | 2751 | 365 | 345 | 370 |
3 ½ |
826501054 | 350 | 0.61 | 0.969 | 1.032 | 1.208 | 1833 | 3557 | 440 | 415 | 460 |
3 ½ |
826501057 | 500 | 0.73 | 1.091 | 1.154 | 1.330 | 2565 | 4771 | 535 | 500 | 575 | 4 |
826501060 | 750 | 0,90 | 1.256 | 1.319 | 1.495 | 3760 | 6726 | 655 | 610 | 745 | 4 |
826501062 | 1000 | 1.06 | 1.412 | 1.475 | 1.711 | 4958 | 8869 | 755 | 690 | 890 | 5 |