MV 105 Indulink CU/ XLPE/ CT/ PVC 5 kV 100% and 133% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable.

Tecnical Data


COPPER CONDUCTOR, 5 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
824601045 4 0.21 0.469 0.531 0.677 309 759 110 120 3
824601047 2 0.27 0.522 0.585 0.731 436 986 145 155 3
824601048 1 0.30 0.554 0.617 0.763 522 1136 175 180 3
824601049 1/0 0.33 0.591 0.654 0.800 630 1325 200 210 220 3
824601050 2/0 0.37 0.631 0.694 0.870 765 1605 225 235 250 3
824601051 3/0 0.42 0.677 0.740 0.916 934 1895 270 270 290 3
824601052 4/0 0.47 0.731 0.794 0.970 1147 2256 305 310 335

3

824601053 250 0.52 0.774 0.837 1.013 1333 2569 355 345 370

3

824601054 350 0.61 0.869 0.932 1.108 1812 3362 430 415 460

3 ½

824601057 500 0.73 0.991 1.054 1.230 2543 4558 530 505 580 3 ½
824601060 750 0,90 1.156 1.219 1.395 3739 6489 665 630 750 4
824601062 1000 1.06 1.312 1.375 1.551 4937 8417 770 720 900 5

COPPER CONDUCTOR, 5 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
826401045 4 0.21 0.489 0.552 0.698 313 785 110 120 3
826401047 2 0.27 0.543 0.606 0.752 440 1013 145 155 3
826401048 1 0.30 0.574 0.637 0.783 526 1165 175 180 3
826401049 1/0 0.33 0.612 0.675 0.851 634 1403 200 210 220 3
826401050 2/0 0.37 0.651 0.714 0.890 770 1637 225 235 250 3
826401051 3/0 0.42 0.698 0.761 0.937 939 1928 270 270 290 3
826401052 4/0 0.47 0.752 0.815 0.990 1151 2290 305 310 335

3

826401053 250 0.52 0.795 0.858 1.034 1338 2605 355 345 370

3

826401054 350 0.61 0.889 0.952 1.128 1816 3401 430 415 460

3 ½

826401057 500 0.73 1.011 1.074 1.250 2548 4600 530 505 580 4
826401060 750 0,90 1.177 1.240 1.416 3743 6537 665 630 750 4
826401062 1000 1.06 1.332 1.395 1.571 4941 8469 770 720 900 5