MV 105 Indulink CU/ XLPE/ CT/ PVC 35 kV 100% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable.

Data


COPPER CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
825001049 1/0 0.33 1.081 1.144 1.320 735 2272 215 215 220 4
825001050 2/0 0.37 1.120 1.183 1.359 870 2533 255 245 250 4
825001051 3/0 0.42 1.167 1.230 1.406 1.039 2854 290 275 285 4
825001052 4/0 0.47 1.221 1.284 1.460 1252 3253 330 315 335 5
825001053 250 0.52 1.264 1.327 1.503 1438 3597 365 345 370 5
825001054 350 0.61 1.359 1.422 1.598 1917 4456 440 415 455 5
825001057 500 0.73 1.481 1.544 1.779 2648 5938 535 500 565

5

825001060 750 0.90 1.646 1.709 1.945 3844 8004 655 610 730

6

825001062 1000 1.06 1.802 1.865 2.100 5042 10058 755 690 870

6