Share:     

Download:

MV 105 Indulink AL/ XLPE/ WS/ PVC 5 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: one-third neutral concentric round annealed bare copper wires elically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energyc

Data


ALUMINUM CONDUCTOR, 5 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINLA CONDUCTOR DIAMETER (inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
83230104540.210.4690.5310.7948819655585933
83230104720.270.5220.5850.8781401969031151253
83230104810.300.5540.6170.9091761969711351403
8323010491/00.330.5910.6540.94622319610561551603
8323010502/00.370.6310.6940.98627922911811751853
8323010513/00.420.6770.7401.03235429513612102103
8323010524/00.470.7310.7941.0864453601564240245

3 ½

8323010532500.520.7740.8371.1305274261748280270

3 ½

8323010543500.610.8690.9321.2247365892198340325

3 ½

8323010575000.730.9911.0541.346106181928494254004
8323010607500,901.1561.2191.6121592125241435455055
83230106210001.061.3121.3751.8282133167054396455906

ALUMINUM CONDUCTOR, 5 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINLA CONDUCTOR DIAMETER (inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)
83400104540.210.4890.5520.8448819682385933
83400104720.270.5430.6060.8981401969311151253
83400104810.300.5740.6370.93017619610011351403
8340010491/00.330.6120.6750.96722319610871551603
8340010502/00.370.6510.7141.00627922912131751853
8340010513/00.420.6980.7611.05335429513942102103
8340010524/00.470.7520.8151.1074453601599240245

3 ½

8340010532500.520.7950.8581.1505274261784280270

3 ½

8340010543500.610.8890.9521.2447365892237340325

4

8340010575000.731.0111.0741.367106181928914254004
8340010607500,901.1771.2401.6331592125241935455055
83400106210001.061.3321.3951.8482133167054966455906