• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 105 Indulink AL/ XLPE/ WS/ PVC 25 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: one-third neutral concentric round annealed bare copper wires elically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energyc

Data


ALUMINUM CONDUCTOR, 25 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM. (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
832601048 1 0.30 0.874 0.937 1.229 176 196 1497 150 145 3 ½
832601049 1/0 0.33 0.911 0.974 1.266 223 196 1599 170 165 3 ½
832601050 2/0 0.37 0.950 1.013 1.306 279 229 1742 200 190 4
832601051 3/0 0.42 0.997 1.060 1.352 354 295 1942 225 215 4
832601052 4/0 0.47 1.051 1.114 1.406 445 360 2171 260 245 4
832601053 250 0.52 1.094 1.157 1.449 527 426 2374 290 270 5
832601054 350 0.61 1.189 1.252 1.544 736 589 2867 350 330

5

832601057 500 0.73 1.311 1.374 1.726 1061 819 3769 430 400

5

832601060 750 0.90 1.476 1.539 1.992 1.592 1252 5214 540 490

6

832601062 1000 1.06 1.631 1.694 2.147 2.133 1.670 6393 640 565 6

ALUMINUM CONDUCTOR, 25 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2)
834301048 1 0.30 0.994 1.057 1.349 176 196 1732 150 145 4
834301049 1/0 0.33 1.031 1.094 1.387 223 196 1841 170 165 4
834301050 2/0 0.37 1.071 1.134 1.426 279 229 1990 200 190 4
834301051 3/0 0.42 1.117 1.180 1.472 354 295 2199 225 215 4
834301052 4/0 0.47 1.171 1.234 1.526 445 360 2437 260 245 5
834301053 250 0.52 1.215 1.278 1.570 527 426 2648 290 270 5
834301054 350 0.61 1.309 1.372 1.724 736 589 3351 350 330

5

834301057 500 0.73 1.431 1.494 1.846 1061 819 4093 430 400

6

834301060 750 0.90 1.596 1.659 2.112 1592 1252 5585 540 490

6

834301062 1000 1.06 1.752 1.815 2.268 2133 1670 6790 640 565 7