• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 105 Indulink AL / XLPE / CT / PVC 8 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).•

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric EnergyUL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables
IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 8 kV 100 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL INSULATION DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY(3)
831901045 4 0.21 0.518 0.581 0.727 88 128 619 94 98 3
831901047 2 0.27 0.572 0.635 0.781 140 139 727 130 130 3
831901048 1 0.30 0.604 0.667 0.842 176 146 845 150 145 3
831901049 1/0 0.33 0.641 0.704 0.880 223 154 933 170 165 170 3
831901050 2/0 0.37 0.680 0.743 0.919 279 163 1033 200 190 195 3
831901051 3/0 0.42 0.727 0.790 0.966 354 173 1158 225 215 225 3
831901052 4/0 0.47 0.781 0.844 1.020 445 185 1309 260 245

260

3
831901053 250 0.52 0.824 0.887 1.063 527 194 1439 290 270

290

3
831901054 350 0.61 0.919 0.981 1.157 736 214 1753 350 330

360

3 ½
831901057 500 0.73 1.041 1.104 1.279 1061 241 2212 430 400 450 4
831901060 750 0.90 1.206 1.269 1.445 1592 277 2926 540 490 585 5
831901062 1000 1.06 1.361 1.424 1.600 2133 310 3638 640 565 705 5

ALUMINUM CONDUCTOR, 8 kV 133 % INSULATION LEVEL, 140 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY(3)
833701045 4 0.21 0.569 0.631 0.777 88 138 688 94 98 3
833701047 2 0.27 0.622 0.685 0.861 140 150 849 130 130 3
833701048 1 0.30 0.654 0.717 0.893 176 157 922 150 145 3
833701049 1/0 0.33 0.691 0.754 0.930 223 165 1014 170 165 170 3
833701050 2/0 0.37 0.731 0.794 0.970 279 174 1116 200 190 195 3
833701051 3/0 0.42 0.777 0.840 1.016 354 184 1245 225 215 225 3
833701052 4/0 0.47 0.831 0.894 1.070 445 195 1399 260 245

260

3
833701053 250 0.52 0.874 0.937 1.113 527 205 1532 290 270

290

3 ½
833701054 350 0.61 0.969 1.032 1.208 736 225 1853 350 330

360

3 ½
833701057 500 0.73 1.091 1.154 1.330 1061 252 2321 430 400 450 4
833701060 750 0,90 1.256 1.319 1.495 1592 287 3047 540 490 585 5
833701062 1000 1.06 1.412 1.475 1.711 2133 321 3963 640 565 705 5