• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 105 Indulink AL / XLPE / CT / PVC 5 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).•

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric EnergyUL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables
IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 5 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL INSULATION DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY(3)
831801045 4 0.21 0.469 0.531 0.677 88 117 555 85 93 3
831801047 2 0.27 0.522 0.585 0.731 140 129 660 115 125 3
831801048 1 0.30 0.554 0.617 0.763 176 136 726 135 140 3
831801049 1/0 0.33 0.591 0.654 0.800 223 144 810 155 160 170 3
831801050 2/0 0.37 0.631 0.694 0.870 279 152 954 175 185 195 3
831801051 3/0 0.42 0.677 0.740 0.916 354 162 1077 210 210 225 3
831801052 4/0 0.47 0.731 0.794 0.970 445 174 1223 240 245

260

3
831801053 250 0.52 0.774 0.837 1.013 527 183 1350 280 270

290

3
831801054 350 0.61 0.869 0.932 1.108 736 204 1657 340 325

360

3 ½
831801057 500 0.73 0.991 1.054 1.230 1061 230 2108 425 400 455 3 ½
831801060 750 0.90 1.156 1.219 1.395 1592 266 2810 545 505 595 4
831801062 1000 1.06 1.312 1.375 1.551 2133 300 3511 645 590 715 5

ALUMINUM CONDUCTOR, 5 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY(3)
833601045 4 0.21 0.489 0.552 0.698 88 121 581 85 93 3
833601047 2 0.27 0.543 0.606 0.752 140 133 687 115 125 3
833601048 1 0.30 0.574 0.637 0.783 176 140 755 135 140 3
833601049 1/0 0.33 0.612 0.675 0.851 223 148 888 155 160 170 3
833601050 2/0 0.37 0.651 0.714 0.890 279 157 986 175 185 195 3
833601051 3/0 0.42 0.698 0.761 0.937 354 167 1110 210 210 225 3
833601052 4/0 0.47 0.752 0.815 0.990 445 178 1258 240 245

260

3
833601053 250 0.52 0.795 0.858 1.034 527 188 1386 280 270

290

3
833601054 350 0.61 0.889 0.952 1.128 736 208 1696 340 325

360

3 ½
833601057 500 0.73 1.011 1.074 1.250 1061 235 2151 425 400 455 3 ½
833601060 750 0,90 1.177 1.240 1.416 1592 270 2857 545 505 595 4
833601062 1000 1.06 1.332 1.395 1.571 2133 304 3563 645 590 715 5