Share:     

Download:

MV 90 Indulink AL / XLPE / CT / PVC 8 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).•

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric EnergyUL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables
IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 8 kV 100 % INSULATION LEVEL, 115 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)TRAY (3)
84070104540.210.5180.5810.7278812861984913
84070104720.270.5720.6350.7811401397271151203
84070104810.300.6040.6670.8421761468451301353
8407010491/00.330.6410.7040.8802231549331501551503
8407010502/00.370.6800.7430.91927916310331751751753
8407010513/00.420.7270.7900.96635417311582002002003
8407010524/00.470.7810.8441.0204451851309230230230

3

8407010532500.520.8240.8871.0635271941439255250260

3

8407010543500.610.9190.9811.1577362141753310305320

3 ½

8407010575000.731.0411.1041.279106124122123853704004
8407010607500.901.2061.2691.445159227729264854555255
84070106210001.061.3611.4241.600213331036385655256305

ALUMINUM CONDUCTOR, 8 kV 133 % INSULATION LEVEL, 140 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)TRAY (3)
84250104540.210.5690.6310.7778813868884913
84250104720.270.6220.6850.8611401508491151203
84250104810.300.6540.7170.8931761579221301353
8425010491/00.330.6910.7540.93022316510141501551503
8425010502/00.370.7310.7940.97027917411161751751753
8425010513/00.420.7770.8401.01635418412452002002003
8425010524/00.470.8310.8941.0704451951399230230230

3

8425010532500.520.8740.9371.1135272051532255250260

3 ½

8425010543500.610.9691.0321.2087362251853310305320

3 ½

8425010575000.731.0911.1541.330106125223213853704004
8425010607500.901.2561.3191.495159228730474854555255
84250106210001.061.4121.3951.711213332139635655256305