Share:     

Download:

MV 90 Indulink AL / XLPE / CT / PVC 35 kV 100% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric EnergyUL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables
IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINAL CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM.(inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)TRAY (3)
8410010491/00.331.0811.1441.32022324917571501501504
8410010502/00.371.1201.1831.35927925718811751701704
8410010513/00.421.1671.2301.40635426720362002002004
8410010524/00.471.2211.2841.46044527922212302302305
8410010532500.521.2641.3271.50352728823782552602605
8410010543500.611.3591.4221.59873630927513103203205
8410010575000.731.4811.5441.77910613353488385395395

5

8410010607500.901.6461.7091.94515923714324485455515

6

84100106210001.061.8021.8652.100213340551525655256206