Share:     

Download:

MV 105 Indulink AL / XLPE / CT / PVC 25 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).•

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric EnergyUL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables
IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 25 kV 100 % INSULATION LEVEL, 260 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINLA CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM. (inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)TRAY(3)
83210104810.300.8740.9371.11317620413031501453 ½
8321010491/00.330.9110.9741.15022321214061701651703 ½
8321010502/00.370.9501.0131.18927922115212001901953 ½
8321010513/00.420.9971.0601.23635423116652252152253 ½
8321010524/00.471.0511.1141.29044524218362602452604
8321010532500.521.0941.1571.33352725219822902702854
8321010543500.611.1891.2521.4277362722333350330

355

4
8321010575000.731.3111.3741.55010612992839430400

445

5
8321010607500.901.4761.5391.77515923353817540490

575

5
83210106210001.061.6311.6941.930213336846076405656906

ALUMINUM CONDUCTOR, 25 kV 133 % INSULATION LEVEL, 320 MILS

PRODUCT CODECOND. SIZE (AWG or kcmil)NOMINLA CONDUCTOR DIAMETER (inches)NOMINAL INSULATION DIAM. (inches)NOMINAL INSULATION SHIELD DIAM. (inches)NOMINAL DIAMETER OVER JACKET (inches)APPROX. WEIGHT (lb/kft)AMPACITY (A)CONDUIT SIZE (inches)
ALUMINUMCOPPERTOTALCONDUIT IN AIR (1)UNDERGROUND DUCT (2)TRAY(3)
83390104810.300.9941.0571.23317623015411501453 ½
8339010491/00.331.0311.0941.27022323816501701651704
8339010502/00.371.0711.1341.31027924717722001901954
8339010513/00.421.1171.1801.35635425719242252152254
8339010524/00.471.1711.2341.41044526821042602452604
8339010532500.521.2151.2781.45352727822582902702855
8339010543500.611.3091.3721.5487362982625350330

355

5
8339010575000.731.4311.4941.73010613253347430400

445

5
8339010607500.901.5961.6591.89515923604172540490

575

6
83390106210001.061.7521.8152.051213339449896405656906