• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 105 Indulink AL / XLPE / CT / PVC 15 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Tree-retardant cross-linked polyethylene (TR-XLPE).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield:5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).•

Standards

ASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric EnergyUL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables
IEEE 1202 – Flame-propagation testing of wire and cable

Tecnical Data


ALUMINUM CONDUCTOR, 15 kV 100 % INSULATION LEVEL, 175 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL INSULATION DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY(3)
832001047 2 0.27 0.682 0.745 0.921 140 163 943 130 130 3
832001048 1 0.30 0.714 0.777 0.953 176 170 1019 150 145 3
832001049 1/0 0.33 0.751 0.814 0.990 223 178 1114 170 165 170 3
832001050 2/0 0.37 0.791 0.854 1.029 279 186 1220 200 190 195 3
832001051 3/0 0.42 0.837 0.900 1.076 354 196 1353 225 215 225 3
832001052 4/0 0.47 0.891 0.954 1.130 445 208 1512 260 245 260 3 ½
832001053 250 0.52 0.934 0.997 1.173 527 218 1648 290 270

290

3 ½
832001054 350 0.61 1.029 1.092 1.268 736 238 1977 350 330

360

4
832001057 500 0.73 1.151 1.214 1.390 1061 264 2456 430 400

450

4
832001060 750 0.90 1.316 1.379 1.555 1592 300 3195 540 490 585 5
832001062 1000 1.06 1.472 1.535 1.770 2133 334 4132 640 565 705 5

ALUMINUM CONDUCTOR, 15 kV 133 % INSULATION LEVEL, 220 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM. (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY(3)
833801047 2 0.27 0.772 0.835 1.011 140 182 1094 130 130 3
833801048 1 0.30 0.804 0.867 1.042 176 189 1174 150 145 3
833801049 1/0 0.33 0.841 0.904 1.080 223 197 1273 170 165 170 3
833801050 2/0 0.37 0.880 0.943 1.119 279 206 1384 200 190 195 3
833801051 3/0 0.42 0.927 0.990 1.166 354 216 1523 225 215 225 3
833801052 4/0 0.47 0.981 1.044 1.220 445 227 1689 260 245 260 3
833801053 250 0.52 1.024 1.087 1.263 527 237 1831 290 270

290

3
833801054 350 0.61 1.119 1.181 1.357 736 257 2172 350 330

360

4
833801057 500 0.73 1.241 1.304 1.479 1061 284 2667 430 400

450

5
833801060 750 0.90 1.406 1.469 1.705 1592 320 3620 540 490 585 5
833701062 1000 1.06 1.561 1.624 1.860 2133 353 4394 640 565 705 6