• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 105 EPRONAX CU/ EPR/ WS/ PVC 35 kV 100% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper tape shield: one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC). •

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy

Data


ALUMINUM CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM. (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY(3)
831201049 1/0 0.33 1.081 1.144 1.320 223 249 1941 170 165 170 4
831201050 2/0 0.37 1.120 1.183 1.320 279 257 2076 200 190 195 4
831201051 3/0 0.42 1.167 1.230 1.406 354 267 2242 225 215 225 4
831201052 4/0 0.47 1.221 1.284 1.460 445 279 2440 260 245 260 5
831201053 25 0.52 1.264 1.327 1.503 527 288 2608 290 270 285 5
831201054 350 0.61 1.359 1.422 1.598 736 309 3005 350 270 355 5
831201057 500 0.73 1.481 1.544 1.779 1061 335 3772 430 400

445 

5
831201060 750 0.90 1.646 1.709 1.945 1592 371 4651 540 490

575

6
831201062 1000 1.06 1.802 1.709 2.100 2133 405 5517 640 565

690

6