MV 105 EPRONAX CU/ EPR/ CT/ PVC 35 kV 100% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper tape shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy. UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


COPPER CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
824001049 1/0 0.33 1.081 1.144 1.320 986 2456 215 215 220 4
824001050 2/0 0.37 1.120 1.183 1.359 1188 2727 255 245 250 4
824001051 3/0 0.42 1.167 1.230 1.406 1439 3060 290 275 285 4
824001052 4/0 0.47 1.221 1.284 1.460 1756 3472 330 315 335 5
824001053 250 0.52 1.264 1.327 1.503 2034 3827 365 345 370 5
824001054 350 0.61 1.359 1.422 1.598 2750 4710 440 415 455 5
824001057 500 0.73 1.481 1.544 1.779 3846 6222 535 500 565

5

824001060 750 0.90 1.646 1.709 1.945 5643 8330 655 610 730

6

824001062 1000 1.06 1.802 1.865 2.100 7443 10423 755 690 870

6