• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 105 EPRONAX CU/ EPR/ WS/ PVC 15 kV 100% and 133% I.L.

Construction

1- Conductor: Compact class B stranded soft annealed bare copper as per ASTM B-496.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper tape shield: one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC). •

Standards

ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
ASTM B-496 - Standard Specification for Compact Round Concentric-Lay-Stranded Copper Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy

Data


ALUMINUM CONDUCTOR, 15 kV 100 % INSULATION LEVEL, 175 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL ISULATION DIAM. (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY(3)
831001047 2 0.27 0.682 0.745 0.921 140 163 1010 130 130 3
831001048 1 0.30 0.714 0.777 0.953 176 170 1091 150 145 3
831001049 1/0 0.33 0.751 0.814 0.990 223 178 1190 170 165 170 3
831001050 2/0 0.37 0.791 0.854 1.029 279 186 1301 200 190 195 3
831001051 3/0 0.42 0.837 0.900 1.076 354 196 1440 225 215 225 3
831001052 4/0 0.47 0.891 0.954 1.130 445 208 1606 260 245 260 3 ½
831001053 250 0.52 0.934 0.997 1.173 527 218 1749 290 270

290

3 ½
831001054 350 0.61 1.029 1.092 1.268 736 238 2090 350 330

360

4
831001057 500 0.73 1.151 1.214 1.390 1061 264 2585 430 400

450

4
831001060 750 0,90 1.316 1.379 1.555 1592 300 3347 540 490 585 5
831001062 1000 1.06 1.472 1.535 1.770 2133 334 4304 640 565 705 5

ALUMINUM CONDUCTOR, 15 kV 133 % INSULATION LEVEL, 220 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINLA CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM. (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY(3)
833001047 2 0.27 0.772 0.835 1.011 140 182 1185 130 130 3
833001048 1 0.30 0.804 0.867 1.042 176 189 1270 150 145 3
833001049 1/0 0.33 0.841 0.904 1.080 223 197 1375 170 165 170 3
833001050 2/0 0.37 0.880 0.943 1.119 279 206 1493 200 190 195 3 ½
833001051 3/0 0.42 0.927 0.990 1.166 354 216 1639 225 215 225 3 ½
833001052 4/0 0.47 0.981 1.044 1.220 445 227 1814  260 245 260 3 ½
833001053 250 0.52 1.024 1.044 1.263 527 237 1963 290 270

290

3 ½
833001054 350 0.61 1.119 1.181 1.357 736 257 2320 350 330

360

4
833001057 500 0.73 1.241 1.304 1.479 1061 284 2834 430 400

450

5
833001060 750 0,90 1.406 1.469 1.705 1592 320 3815 540 490 585 5
833001062 1000 1.06 1.561 1.624 1.860 2133 353 4615 640 565 705 6