MV 90 EPRONAX AL/ EPR/ CT/ PVC 5 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - StandaASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 5 kV 100 % INSULATION LEVEL, 90 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
839601045 4 0.21 0.469 0.531 0.677 88 117 583 76 86 3
839601047 2 0.27 0.522 0.585 0.731 100 129 692 245 115 3
839601048 1 0.30 0.554 0.617 0.763 176 136 761 120 130 3
839601049 1/0 0.33 0.591 0.654 0.800 223 144 848 140 150 150 3
839601050 2/0 0.37 0.631 0.694 0.870 279 152 995 160 170 170 3
839601051 3/0 0.42 0.677 0.740 0.916 354 162 1121 190 195 200 3
839601052 4/0 0.47 0.731 0.794 0.970 445 174 1272 215 225 230

3

839601053 250 0.52 0.774 0.837 1.013 527 183 1402 250 250 260

3

839601054 350 0.61 0.869 0.932 1.108 736 204 1716 305 305 320

3 ½

839601057 500 0.73 0.991 1.054 1.230 1061 230 2176 380 370 410 3 ½
839601060 750 0.90 1.156 1.219 1.395 1592 266 2891 490 470 530 4
839601062 1000 1.06 1.312 1.375 1.551 2133 300 3603 580 545 640 5

ALUMINUM CONDUCTOR, 5 kV 133 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
841601045 4 0.21 0.489 0.552 0.698 88 121 613 76 86 3
841601047 2 0.27 0.543 0.606 0.752 140 133 723 100 115 3
841601048 1 0.30 0.574 0.637 0.783 176 140 794 120 130 3
841601049 1/0 0.33 0.612 0.675 0.851 223 148 930 140 150 150 3
841601050 2/0 0.37 0.651 0.714 0.890 279 157 1031 160 170 170 3
841601051 3/0 0.42 0.698 0.761 0.937 354 167 1159 190 195 200 3
841601052 4/0 0.47 0.752 0.815 0.990 445 178 1312 215 225 230

3

841601053 250 0.52 0.795 0.858 1.034 527 188 1443 250 250 260

3

841601054 350 0.61 0.889 0.952 1.128 736 208 1761 305 305 320

3 ½

841601057 500 0.73 1.011 1.074 1.250 1061 235 2226 380 370 410 3 ½
841601060 750 0.90 1.177 1.240 1.416 1592 270 2947 490 470 530 4
841601062 1000 1.06 1.332 1.395 1.571 2133 304 3665 580 545 640 5