MV 90 EPRONAX AL/ EPR/ CT/ PVC 8 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - StandaASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 8 kV 100 % INSULATION LEVEL, 115 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
839701045 4 0.21 0.518 0.581 0.727 88 128 656 84 91 3
839701047 2 0.27 0.572 0.635 0.781 140 139 769 115 120 3
839701048 1 0.30 0.604 0.667 0.813 176 146 842 130 135 3
839701049 1/0 0.33 0.641 0.704 0.880 223 154 982 150 150 150 3
839701050 2/0 0.37 0.680 0.743 0.919 279 163 1085 175 175 175 3
839701051 3/0 0.42 0.727 0.790 0.966 354 173 1215 200 200 200 3
839701052 4/0 0.47 0.781 0.844 1.020 445 185 1371 230 230 230

3

839701053 250 0.52 0.824 0.887 1.063 527 194 1504 255 250 260

3

839701054 350 0.61 0.919 0.981 1.157 736 214 1827 310 305 320

3 ½

839701057 500 0.73 1.041 1.104 1.279 1061 241 2298 385 370 400 4
839701060 750 0.90 1.206 1.269 1.445 1592 277 3027 485 455 525 5
839701062 1000 1.06 1.361 1.424 1.600 2133 310 3754 565 525 630 5

ALUMINUM CONDUCTOR, 8 kV 133 % INSULATION LEVEL, 140 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
841701045 4 0.21 0.569 0.631 0.777 88 138 735 84 91 3
841701047 2 0.27 0.622 0.685 0.861 140 150 902 115 120 3
841701048 1 0.30 0.654 0.717 0.893 176 157 979 130 135 3
841701049 1/0 0.33 0.691 0.754 0.930 223 165 1074 150 155 150 3
841701050 2/0 0.37 0.731 0.794 0.970 279 174 1181 175 175 175 3
841701051 3/0 0.42 0.777 0.840 1.016 354 184 1315 200 200 200 3
841701052 4/0 0.47 0.831 0.894 1.070 445 195 1476 230 230 230

3

841701053 250 0.52 0.874 0.937 1.113 527 205 1613 255 250 260

3 ½

841701054 350 0.61 0.969 1.032 1.208 736 225 1945 310 305 320

3 ½

841701057 500 0.73 1.091 1.154 1.330 1061 252 2427 385 370 400 4
841701060 750 0.90 1.256 1.319 1.416 1592 287 3171 485 455 525 5
841701062 1000 1.06 1.412 1.475 1.711 2133 321 4104 565 525 630 5