MV 90 EPRONAX AL/ EPR/ CT/ PVC 15 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - StandaASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 15 kV 100 % INSULATION LEVEL, 175 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
839801047 2 0.27 0.682 0.745 0.921 140 163 1010 115 120 3
839801048 1 0.30 0.714 0.777 0.953 176 170 1091 130 135 3
839801049 1/0 0.33 0.751 0.814 0.990 223 178 1190 150 155 150 3
839801050 2/0 0.37 0.791 0.814 1.029 279 186 1301 175 175 170 3
839801051 3/0 0.42 0.837 0.900 1.076 354 196 1440 200 200 200 3
839801052 4/0 0.47 0.891 0.954 1.130 445 208 1606 230 230 230 3 ½
839801053 250 0.52 0.934 0.997 1.173 527 218 1749 255 250 260

3 ½

839801054 350 0.61 1.029 1.092 1.268 736 238 2090 310 305 320

4

839801057 500 0.73 1.151 1.214 1.390 1061 264 2585 385 370 395

4

839801060 750 0.90 1.316 1.379 1.555 1592 300 3347 485 455 515 5
839801062 1000 1.06 1.472 1.535 1.770 2133 334 4304 565 525 620 5

ALUMINUM CONDUCTOR, 15 kV 133 % INSULATION LEVEL, 220 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
841801047 2 0.27 0.772 0.835 1.011 140 182 1185 115 120 3
841801048 1 0.30 0.804 0.867 1.042 176 189 1270 130 135 3
841801049 1/0 0.33 0.841 0.904 1.080 223 197 1375 150 155 150 3
841801050 2/0 0.37 0.880 0.943 1.119 279 206 1493 175 175 170 3 ½
841801051 3/0 0.42 0.927 0.990 1.166 354 216 1639 200 200 200 3 ½
841801052 4/0 0.47 0.981 1.044 1.220 445 227 1814 230 230 230 3 ½
841801053 250 0.52 1.024 1.087 1.263 527 237 1963 255 250 260

3 ½

841801054 350 0.61 1.119 1.181 1.357 736 257 2320 310 305 320

4

841801057 500 0.73 1.241 1.304 1.479 1061 284 2834 385 370 395

5

841801060 750 0.90 1.406 1.469 1.705 1592 320 3815 485 455 515 5
841801062 1000 1.06 1.561 1.624 1.860 2133 353 4615 565 525 620 6