MV 90 EPRONAX AL/ EPR/ CT/ PVC 25 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: 5 mils bare copper tape helically applied with 25 % minimum overlap.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

ASTM B-400 - StandaASTM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribution of Electric Energy UL 1685 - Safety Vertical-Tray Fire-Propagation and Smoke-Release Test for Electrical and Optical-Fiber Cables IEEE 1202 – Flame-propagation testing of wire and cable

Data


ALUMINUM CONDUCTOR, 25 kV 100 % INSULATION LEVEL, 260 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
839901048 1 0.30 0.874 0.937 1.113 176 204 1420 130 135 3 ½
839901049 1/0 0.33 0.911 0.974 1.150 223 212 1530 150 155 150 3 ½
839901050 2/0 0.37 0.950 1.013 1.189 279 221 1652 175 175 170 3 ½
839901051 3/0 0.42 0.997 1.060 1.236 354 231 1805 200 200 200 3 ½
839901052 4/0 0.47 1.051 1.114 1.290 445 242 1986 230 230 230 4
839901053 250 0.52 1.094 1.157 1.333 527 252 2141 255 250 260 4
839901054 350 0.61 1.189 1.252 1.427 736 272 2509 310 305 320

4

839901057 500 0.73 1.311 1.374 1.550 1061 299 3039 385 370 395

5

839901060 750 0.90 1.476 1.539 1.775 1592 335 4048 485 455 515 5
839901062 1000 1.06 1.631 1.694 1.930 2133 368 4868 565 525 620 6

 ALUMINUM CONDUCTOR, 25 kV 133 % INSULATION LEVEL, 320 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM. (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
841901048 1 0.30 0.994 1.057 1.233 176 230 1698 130 135 3 ½
841901049 1/0 0.33 1.031 1.094 1.270 223 238 1816 150 155 150 4
841901050 2/0 0.37 1.071 1.134 1.310 279 247 1947 175 175 170 4
841901051 3/0 0.42 1.117 1.180 1.356 354 257 2109 200 200 200 4
841901052 4/0 0.47 1.171 1.234 1.410 445 268 2302 230 230 230 4
841901053 250 0.52 1.215 1.278 1.453 527 278 2467 255 250 260 5
841901054 350 0.61 1.309 1.372 1.548 736 298 2855 310 305 320 5
841901057 500 0.73 1.431 1.494 1.730 1061 325 3606 385 370 395 5
841901060 750 0.90 1.596 1.659 1.895 1592 360 4470 485 455 515 6
841901062 1000 1.06 1.752 1.815 2.051 2133 394 5322 565 525 620 6