• Sales +1 (587) 885-1422  •  Follow us  

Share:     

Download:

MV 105 EPRONAX AL/ EPR/ WS/ PVC 35 kV 100% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

STM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy

Data


 ALUMINUM CONDUCTOR, 35 kV 100 % INSULATION LEVEL, 345 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
831201049 1/0 0.33 1.081 1.144 1.436 223 196 2131 170 165 170 4
831201050 2/0 0.37 1.120 1.183 1.476 279 229 2293 200 190 195 4
831201051 3/0 0.42 1.167 1.230 1.522 354 295 2517 225 215 225 4
831201052 4/0 0.47 1.221 1.284 1.576 445 360 2772 260 245 260 5
831201053 250 0.52 1.264 1.327 1.619 527 426 2997 290 270 285 5
831201054 350 0.61 1.359 1.422 1.774 736 589 3736 350 330 355 5
831201057 500 0.73 1.481 1.544 1.896 1061 819 4517 430 400 445

5

831201060 750 0.90 1.646 1.709 2.162 1592 1252 6069 540 490 575

6

831201062 1000 1.06 1.802 1.865 2.317 2133 1670 7325 640 565 690 6