MV 105 EPRONAX AL/ EPR/ WS/ PVC 25 kV 100% and 133% I.L.

Construction

1- Conductor: Class B compact stranded 1350 aluminum as per ASTM B-400.
2- Conductor shield: Extruded thermoset semi-conducting stress control layer.
3- Insulation: Ethylene propylene rubber (EPR).
4- Insulation shield: Extruded thermoset strippable semi-conducting insulation shield.
5- Copper wires shield: one-third neutral concentric round annealed bare copper wires helically applied over the insulation shield.
6- Jacket: black flame retardant, sunlight and oil resistant I polyvinyl chloride (PVC).

Standards

STM B-400 - Standard Specification for Compact Round Concentric-Lay-Stranded Aluminum 1350 Conductors ASTM B-3 - Standard Specification for Soft or Annealed Copper Wire
UL 1072 - Medium-Voltage Power Cables
ICEA S-93-639 - 5-46 kV Shielded Power Cable for use in the Transmission and Distribubtion of Electric Energy

Data


ALUMINUM CONDUCTOR, 25 kV 100 % INSULATION LEVEL, 260 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM.(inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
831101048 1 0.30 0.874 0.937 1.229 176 196 1613 150 145 3 ½
831101049 1/0 0.33 0.911 0.974 1.266 223 196 1722 170 165 170 3 ½
831101050 2/0 0.37 0.950 1.013 1.306 279 229 1873 200 190 195 3 ½
831101051 3/0 0.42 0.997 1.060 1.352 354 295 2082 225 215 225 3 ½
831101052 4/0 0.47 1.051 1.114 1.406 445 360 2321 260 245 260 4
831101053 250 0.52 1.094 1.157 1.449 527 426 2533 290 270 285 4
831101054 350 0.61 1.189 1.252 1.544 736 589 3044 350 330 355

4

831101057 500 0.73 1.311 1.374 1.726 1061 819 3969 430 400 445

5

831101060 750 0.90 1.476 1.539 1.992 1592 1252 5446 540 490 575 5
831101062 1000 1.06 1.631 1.694 2.147 2133 1670 6654 640 565 690 6

ALUMINUM CONDUCTOR, 25 kV 133 % INSULATION LEVEL, 320 MILS

PRODUCT CODE COND. SIZE (AWG or kcmil) NOMINAL CONDUCTOR DIAMETER (inches) NOMINAL INSULATION DIAM. (inches) NOMINAL INSULATION SHIELD DIAM. (inches) NOMINAL DIAMETER OVER JACKET (inches) APPROX. WEIGHT (lb/kft) AMPACITY (A) CONDUIT SIZE (inches)
ALUMINUM COPPER TOTAL CONDUIT IN AIR (1) UNDERGROUND DUCT (2) TRAY (3)
833101048 1 0.30 0.994 1.057 1.349 176 196 1889 150 145 3 ½
833101049 1/0 0.33 1.031 1.094 1.387 223 196 2006 170 165 170 4
833101050 2/0 0.37 1.071 1.134 1.426 279 229 2165 200 190 195 4
833101051 3/0 0.42 1.117 1.180 1.472 354 295 2385 225 215 225 4
833101052 4/0 0.47 1.171 1.234 1.526 445 360 2635 260 245 260 4
833101053 250 0.52 1.215 1.278 1.570 527 426 2856 290 270 285 5
833101054 350 0.61 1.309 1.372 1.724 736 589 3582 350 330 355 5
833101057 500 0.73 1.431 1.494 1.846 1061 819 4352 430 400 445 5
833101060 750 0.90 1.596 1.659 2.112 1592 1252 5882 540 490 575 6
833101062 1000 1.06 1.752 1.815 2.268 2133 1670 7124 640 565 690 6